Fire pumps are quintessential to guarantee fire safety of the person as well as property. Therefore, to ensure the effective working and long life of the fire pumps, it is important to understand the problems that might occur in a Fire pump, Various causes behind it and what are the solutions to these problems.
Most of the problems are because of the internal malfunctioning, hence one should know about the different parts of the pump as well.
Below mentioned are some of the problems that might occur in a fire pump.
1. Abnormal Vibrations–
S.no. |
Causes |
Solution |
1. |
Misalignment of pump |
A number of devices are available for measuring alignment offsets including dial indicators and laser alignment tools. Close coupling and Laser Shaft Alignment method can be used to align the pump. |
2. |
Bending of fire pump shaft |
Getting the fire pump straightened or replacing it with the new one |
3. |
Impeller imbalance |
Finding balance by adding or removing material, by drilling, milling, or grinding. |
2. Failure of discharge of water-
S.no. |
Causes |
Solution |
1. |
Size of the pipe is small as compared to the water discharge. |
Change the water pipe to that of suitable size |
2. |
The actual head exceeds the designed head |
Shift to another Fire pump/ change the impeller |
3. |
Presence of air in the suction pipe |
Exhaust the air from the suction pipe |
4. |
Suction head exceeds the designed suction head |
Install fire pump according to the rated suction. |
5. |
Suction pipe, discharge pipe and pump inlet was partially clogged by impurities |
The pipes need to be checked and cleaned up. |
6. |
Pump direction is opposite |
Change the direction accordingly. |
3. Leakage of mechanical seal of fire pump-
S. no. |
Causes |
Solution |
1. |
Spring out of action because of loose fixing of screws |
fastening screw or re-adjusting spring |
2. |
Insufficient spring pressure |
re-adjust the amount of compression spring or change the spring |
3. |
stationary ring assembly skew |
reinstall fire pump stationary ring |
4. |
Wrap or static ring face corrosion, wear or scratches |
repair or replace the bad ring, stationary ring |
5. |
impurities, foreign bodies or medium Crystallization axial movement of ring or support moving between the end face of the stationary ring |
Eliminate impurities, foreign bodies and crystallization, thoroughly clean the sealing element |
6. |
The seal ring assembly/ volume deformation or corrosion |
Reinstall or replace fire pump seal ring |
4. Overheating of fire pump motor-
S.no. |
Causes |
Solutions |
1. |
Pressure tight packing gland or mechanical seal spring tuned too tight |
Re-adjust gland or mechanical seal spring compression. |
2. |
The Range (flow, head) is used more than the fire pump design requirements |
Choose the right motor by series spectrum |
3. |
Fire pump assembly quality is poor; there is friction with the Fire Department or the motor shaft misalignment |
Check the assembly quality, eliminate assembly failure. |
4. |
Media accounted for more than the fire pump motor configuration |
Configure the appropriate fire pump motor. |